Water Chiller Parameter list

Code Menu content Range Ex-factory Company
F01 Temperature return difference 0.3-10 2
F02 Temperature correction -5-5 0
F03 Inlet water temperature correction -5-5 0 minute
F04 Start delay 1-5 3 minute
F05 Menu password 0~9999 8888 /
F06 Defrosting time 1-45 3 minute
F07 Defrosting cycle 10-240 60 minute
F08 Fahrenheit and Celsius display switching 0~1 0 /
F09 Upper temperature limit 2-43 40
F10 Lower temperature limit

1-43

2
F11 Compressor current overload protection

0-25

12 A
F12 Overload delay protection

2-29

10 Second
F13 Display temperature switch 0:In 1:Out 0 /
F14 Ozone running time

0-180

60

minute

F15 Fan overload protection 0-10 5 A
F16 Water pump overload protection 0-6 5 A
F1-01 Water pump impeller (stuck) 0-220 200 HZ
F1-02 Water pump impeller rotation frequency(lack water) 220-320 300 HZ
F1-03 Water pump impeller rotation frequency(no water) 320-340 320 HZ
F18 Chiller pressure detection 0:ON 1:OFF 0
F19 Temperature difference 0-45 5
F20 Detection function 0:ON 1:OFF 1 /
F21 Standby display

0-200

15

minute

Water Chiller Parameter Annotation

F01

When the water temperature is equal to or higher than the target temperature, start cooling; when the water

temperature is equal to or less than the target temperature , start heating

F02 When the displayed temperature deviates from the actual temperature, this function can be used for calibration.
F03

When there is a deviation between the inlet water temperature and the displayed water temperature, you can

use this function to correct it. When you click on the correction, a pop-up prompt will appear to confirm the

current temperature and then enter the correction numeric keyboard pop-up window.

F04

After clicking on, there will be a 3-minute countdown. If the water pump does not report an error, the

compressor and fan will be started.

F05 Click setting and you will be prompted to enter the password to enter the settings.
F06 Defrost operation, and it will exit defrost when the time is over
F07

Defrost will be executed when the continuous operation time of

electric heating reaches the factory setting

F08 Set to 0: Celsius mode set to 1: Fahrenheit mode
F09

Limit the maximum value of the target temperature, when the temperature exceeds this set value, the

over-temperature protection will be triggered.

F09

Limit the maximum value of the target temperature, when the temperature exceeds this set value, the

over-temperature protection will be triggered.

F10

Limit the lowest value of the target temperature, when the temperature is lower than this setting, the ultra-low

temperature protection will be triggered.

F11 The current exceeds this setting value and will triggers overload protection when the compressor is working .
F12

If the compressor of working current overload duration is greater than this setting value, then will trigger this

protection.

F13 Set to 0: to display the internal temperature of the evaporator; to 1: to display the water inlet temperature
F14

After press the “Ozone” button , it will start counting down according to this setting time. When the countdown

ends, it will stop the “Ozone” to continue working.

F15

The current of the fan exceeds this setting value when the fan is working then will triggers the overload

protection

F16

The current is lower than this setting value when the water pump is working and then will triggers the overload

protection.The monitoring starts after 5 minutes of power on.

F1-01 The water pump is stuck and there is no water flow
F1-02 The water pump is running normally and the water flow is small

F1-03

The water pump is running normally but no water flow in the waterway
F18 Detect the refrigerant pressure of the chiller system through a pressure switch
F19

The absolute value of the subtraction between the monitored inlet water temperature and the monitored

evaporator internal temperature

F20 Set to 0: All detection function device will invalid. Set to 1: All detection function device will be valid
F21 Automatic screen save time